Cartridge Globe Valves control hot and chilled water for VAV terminals fan coil units, small re-heaters and re-coolers in temperature controllers.
- Long stroke allows wider range of control
- Soft valve seat provides low leakage rate
- Inserts for 1/2 in and 3/4 in valves are changeable without draining valve when used with an insert replacement tool
- Threaded plastic cover/manual handle allows manual operation
- Easily installed in areas where space is limited
- Used with M6410A1029/M7410F1000/M6435A1004/M7435F1001/MP958 cartridge globe valve actuator
- Brass seat/ cartridge/ plug/ ball/ disc and stainless steel stem
- 1/4 in stem travel
- Equal percentage flow characteristic
- Chilled or hot water with up to 50% glycol controlled fluid, not for use with steam or fuels
- Stem down to close valve action
- 36 to 230 deg F ambient temperature